首页|A STUDY ON REMOVING O_2 IN BOILER FEEDWATER IN COMBINATION WITH A CATALYTIC BURNING PROCESS

A STUDY ON REMOVING O_2 IN BOILER FEEDWATER IN COMBINATION WITH A CATALYTIC BURNING PROCESS

扫码查看
The deoxygenation combustion reaction was researched in a fixed bed reactor and with the Pt catalyst in a cycle reactor。 The fixed bed reactor working at 360 ℃ can reduced the O_2 contents in tail gas to 1000 ppm, The cycle reactor were combined with the gas liquid contacter to remove the O_2 in the boiler feedwater。 The combined operation showed that the O_2 content in the water could be reduced to 0。1 mg/l。

deoxygenationcatalytic combustionboiler feedwater

Wang Guangrun、Yao Zutao、Ding Jie

展开 >

Dept. of Chemical Engineering,Tsinghua University Beijing 100084, P.R.China

Beijing(CN)

1996 Asian-Pacific chemical reaction engineering forum(APCRE'96)

129-134