首页|A STUDY ON REMOVING O_2 IN BOILER FEEDWATER IN COMBINATION WITH A CATALYTIC BURNING PROCESS
A STUDY ON REMOVING O_2 IN BOILER FEEDWATER IN COMBINATION WITH A CATALYTIC BURNING PROCESS
扫码查看
点击上方二维码区域,可以放大扫码查看
原文链接
NETL
The deoxygenation combustion reaction was researched in a fixed bed reactor and with the Pt catalyst in a cycle reactor。 The fixed bed reactor working at 360 ℃ can reduced the O_2 contents in tail gas to 1000 ppm, The cycle reactor were combined with the gas liquid contacter to remove the O_2 in the boiler feedwater。 The combined operation showed that the O_2 content in the water could be reduced to 0。1 mg/l。
deoxygenationcatalytic combustionboiler feedwater
Wang Guangrun、Yao Zutao、Ding Jie
展开 >
Dept. of Chemical Engineering,Tsinghua University Beijing 100084, P.R.China
Beijing(CN)
1996 Asian-Pacific chemical reaction engineering forum(APCRE'96)