首页|On-site diagnosis of XLPE transmission power cables with Damped AC technique

On-site diagnosis of XLPE transmission power cables with Damped AC technique

扫码查看
Diagnostics of HV power cables are playing an important role in the meaning of two aspects: 1) on-site diagnostic of new installation, where a commissioning test has to prove the absence of any defects in the cable insulation and accessories, after transportation and installation。 2) On-site diagnostic of a serviced aged power cable where the condition after a period in service or information about workmanship of repairs has to be known。 As it is known some installation defects can result in breakdown even after a successful after-laying test。 Obtaining more diagnostic parameters like; Withstand Voltage, Partial Discharges (PD) and Dielectric Loss (tan δ), providing a indication of insulation condition and accessory performance。 In this paper several examples of on-site tests on new and serviced aged XLPE HV power cables will be discussed。 Examples of: after-repair, after-laying, and condition assessment tests will be presented as performed with Damped AC diagnostics。

HV power cablescondition evaluationon-site diagnostics

P Cichecki、E Gulski、J J Smit、L Chmura、R Jongen

展开 >

Delft Univ. of Technol., Delft, Netherlands

Seitz Instrum. AG, Niederrohrdorf, Switzerland

San Diego, CA(US)

Conference Record of the 2010 IEEE International Symposium on Electrical Insulation

P.1-5

2010