NETL
Diagnostics of HV power cables are playing an important role in the meaning of two aspects: 1) on-site diagnostic of new installation, where a commissioning test has to prove the absence of any defects in the cable insulation and accessories, after transportation and installation。 2) On-site diagnostic of a serviced aged power cable where the condition after a period in service or information about workmanship of repairs has to be known。 As it is known some installation defects can result in breakdown even after a successful after-laying test。 Obtaining more diagnostic parameters like; Withstand Voltage, Partial Discharges (PD) and Dielectric Loss (tan δ), providing a indication of insulation condition and accessory performance。 In this paper several examples of on-site tests on new and serviced aged XLPE HV power cables will be discussed。 Examples of: after-repair, after-laying, and condition assessment tests will be presented as performed with Damped AC diagnostics。
HV power cablescondition evaluationon-site diagnostics
P Cichecki、E Gulski、J J Smit、L Chmura、R Jongen
展开 >
Delft Univ. of Technol., Delft, Netherlands
Seitz Instrum. AG, Niederrohrdorf, Switzerland
San Diego, CA(US)
Conference Record of the 2010 IEEE International Symposium on Electrical Insulation