首页|The Effect of Contact Structure on Electromagnetic Force

The Effect of Contact Structure on Electromagnetic Force

扫码查看
In order to improve the performance of vacuum interrupter, two types of radial magnetic field (RMF) contact structure were designed for electromagnetic force research。 Electromagnetic force of arc and electric repulsion of move contact was simulated analysis by Ansys software at 25 kA。 The electric repulsion of move contact can be decreased to 4% by improving contact structure at short time withstand current。 It can improve the performance of short time withstand current (STC), peak withstand current and earthing switch making。 The electromagnetic force direction of arc can be improved by improving contact structure。 It can avoid arc erosion in a small area of contact and increase electric endurance performance。 The electromagnetic force of arc can be increased by contact 15° dislocation assemble。 It can increase the electric endurance performance of contact。 The electric repulsion of move contact is about 190 N at 0。5 mm contact gap with arc for both contact structures。

Vacuum interrupterSimulationElectromagnetic force

Min Li、Baochun Song、Anthony Papillon

展开 >

Schneider Electric (Xiamen) Switchgear Equipment Co., Ltd, Xiamen 361000, China

Schneider Electric Co., Ltd, Grenoble, France

International Symposium on Insulation and Discharge Computation for Power Equipment

Wuhan(CN)

The Proceedings of 2023 4th International Symposium on Insulation and Discharge Computation for Power Equipment

1-8

2023