基于配网继电保护整定原则的工程案例分析

扫码查看
现场保护装置存在因电流互感器变比和定值整定范围受限,造成定值无法正常整定的现象.文章根据配网继电保护整定原则,针对具体案例对"退出过流Ⅰ段保护"和"按装置最大值整定"两种场景进行分析,确定"退出过流Ⅰ段保护"可实现级差配合,避免出现各级开关同跳闸、越级跳闸情况,缩小停电范围,提高供电可靠性.
Engineering Case Analysis Based on the Relay Protection Setting Principle for the Distribution Network
Due to the limitation of current transformer ratio and setting range,the setting value of on-site protection device can not be set normally.According to the relay protection setting principle for the distri-bution network,two scenarios of"quitting overcurrent Section I protection"and"setting based on the max-imum value of the device"are analyzed for specific cases,and it is determined that"quitting overcurrent Section I protection"can realize graded coordination,avoid simultaneous or override tripping of switches at all levels,reduce the scope of power outage and improve the reliability of power supply.

distribution networkrelay protectionsettingsetting calculationfeeder line switchgraded coordinationselectivity