一起110kV变电站10kV母线失压事件分析

扫码查看
文章介绍了一起110 kV变电站10 kV母线失压事故的原因分析.主要原因是10 kV开关柜因设备老化引发单相接地故障,进而演变成两相和三相故障,最终导致开关柜爆炸及故障进一步发展到主变低压侧,从而造成 10 kV母线失压.基于故障原因分析,从管理和技术方面提出了故障防范建议,以此来更好地保障电力系统安全稳定运行.
Analysis of a 10 kV Bus Voltage Loss Fault in a 110 kV Substation
This paper analyzes the cause of a 10 kV bus voltage loss in a 110 kV substation.The main rea-son is that the aging of the equipment causes the single-phase grounding fault of the 10 kV switch cabinet,which then develops into two-phase and three-phase faults,and finally leads to the explosion of the switch cabinet,and the fault of the low-voltage side of the main transformer,resulting in the 10 kV bus voltage voltage loss.Based on the fault causes analysis,this paper puts forward some fault prevention suggestions from the aspects of management and technology,so as to ensure the safe and stable operation of power sys-tem.

bus voltage lossfaultswitch cabinetsingle phase grounding