首页|一起110kV主变铁心多点特殊接地故障诊断消缺的典型案例分析

一起110kV主变铁心多点特殊接地故障诊断消缺的典型案例分析

扫码查看
在例行带电检测过程中,发现某110kV主变本体油色谱分析存在轻微异常,通过长时间采样跟踪发现氢气和总烃含量呈持续增长态势,并在近期采样结果中远超规定值;在完成各项常规及特殊试验诊断后,并未发现明显异常项;经抽油吊检处理,发现内部铁心引线存在明显烧蚀痕迹,系铁心引线与硅钢片短路造成变压器内部铁心多点接地形成的环流放电所致,并直接导致油色谱数据异常.确定故障原因和缺陷位置后,对故障部件进行了更换处理,保证了运行设备的安全稳定.
Analysis of Typical Case of Diagnosis and Elimination of Multiple Special Grounding Faults in Core of 110kV Main Transformer
During the routine live detection process,it is found that there is a slight ab-normality in the oil chromatography analysis of a certain 110kV main transformer.Through long-term sampling and tracking,it is found that the hydrogen and total hydro-carbon content showed a continuous growth trend.And in recent sampling results,the hydrogen and total hydrocarbon content are far exceeded the specified values.After completing various routine and special test diagnoses,no obvious abnormalities are found.So oil is extracted and inspection is conducted,which found that there is obvious sign of erosion on the internal iron core lead.The sign is caused by a short circuit be-tween the iron core lead and the silicon steel sheet,which resulted in circulating current discharge and abnormal oil chromatogram data.After determining the cause of the mal-function and the location of the defect,the faulty components are replaced to ensure the safety and stability of the operating equipment.

Main transformerAbnormal oil chromatogramExperimental analysisMulti-point grounding

胡露、舒鸿科、肖懿、代禄喻、刘明军、夏维建

展开 >

国网永川供电公司,重庆 402160

主变压器 油色谱异常 试验分析 多点接地

2025

变压器
沈阳变压器研究所

变压器

影响因子:0.825
ISSN:1001-8425
年,卷(期):2025.62(1)