喷淋工况下闭式热源塔传热特性

Performance of closed heat source tower under spraying conditions

贺志明 李念平 成剑林 陈琦 张鼎
土木建筑与环境工程2015,Issue(1) :35-39,54.DOI:10.11835/j.issn.1674-4764.2015.01.007

喷淋工况下闭式热源塔传热特性

Performance of closed heat source tower under spraying conditions

贺志明 1李念平 1成剑林 1陈琦 1张鼎1
扫码查看

作者信息

  • 1. 湖南大学土木工程学院,长沙410082
  • 折叠

摘要

建立了闭式热源塔的数学模型,利用MATLAB自编程序,实现了对喷淋工况下热源塔的数值模拟,并将计算结果与实验结果进行了比较。利用程序得到了喷淋工况下的闭式热源塔内喷淋溶液、载热流体、空气焓值的分布,结果表明:塔内空气焓值呈线性分布,翅片换热器上半部分换热效果比下半部分好,塔的中部位置附近最先出现结霜现象,空气干球温度高于5畅1℃,相对湿度高于75%,闭式热源塔热泵系统没有结霜风险,可以停止喷淋泵,有助减少热泵系统的运行能耗。

Abstract

Compling a program by matlab to investigate closed heat source tower operating under spraying conditions .The numerical results of the spray solution temperature , the refrigerant temperature , air enthalpy value were compared with the experimental ones . The program was used to calculate the distribution of the spray temperature ,refrigerant temperature ,air enthalpy in the closed heat source tower under spraying conditions .Some results were obtained .The air enthalpy is linear distribution and upper fin heat exchanger heat transfer effect is better than the lower part .The center of the tower is firstly frosting . The air dry bulb temperature is above 5.1 ℃and relative humidity is above 75% .The closed heat source heat pump system is without risk of frost ,so stopping the spray pump is viable in order to reduce the energy consumption of the operation of the heat pump system .

关键词

模型简化/数值模拟/传热/热源塔/喷淋工况

Key words

model reduction/numerical simulation/heat transfer/heat source tower/spraying conditions