首页|基于脉冲电流法的局放实时监测技术在配电网中的应用

基于脉冲电流法的局放实时监测技术在配电网中的应用

扫码查看
局部放电(局放)是开关柜发生故障完全击穿前的典型特征,局放监测可以有效避免事故发生.为克服离线测量需停电和传统在线监测方案易受干扰或无法直接获得局放数值的弱点,基于物联网技术设计了一种全新的方案实现局放实时无线监测和诊断.其利用开关柜现有带电显示装置形成符合GB/T 7354-2018标准的脉冲电流法测量回路,采集数据经校准后通过无线通信方式发送至云端系统.试验验证了该方案具有局放测量和缺陷类型识别的良好性能,现被应用于某已投运配电站所,具有较高工程价值.
Application of PD Real-Time Monitoring Technology Based on Pulse Current Method in Distribution Network
Partial discharge(PD)is a typical characteristic of switchgear failure before complete breakdown,so PD monitoring can effec-tively avoid accidents.In order to overcome the weaknesses of offline measurement requiring power outage and traditional online monitoring scheme being susceptible to interference or unable to obtain direct access to the local discharge values,a new scheme based on the Internet of Things(IoT)technology is designed to realize real-time wireless monitoring and diagnosis of partial discharge.It utilizes the existing charged display device of the switchgear to form a pulse current method measurement loop in line with the GB/T 7354-2018 standard,and the collected data is calibrated and sent to the cloud system through wireless communication.Tests have verified that the scheme has good performance in partial discharge measurements and defect-type identification,and is now applied to a commissioned distribution substation with high engineering value.

pulse current methodpartial dischargeswitchgearwireless monitoringInternet of Things

欧阳自强、董晓峰、许小坤、刘杰

展开 >

国网江苏省电力有限公司苏州供电分公司,江苏 苏州 215004

施耐德电气(中国)有限公司上海分公司,上海 200062

施耐德电气(厦门)开关设备有限公司,福建 厦门 361006

脉冲电流法 局部放电 开关柜 无线监测 物联网

2025

电工电气
苏州电器科学研究所有限公司

电工电气

影响因子:0.254
ISSN:1007-3175
年,卷(期):2025.(1)