电工技术2024,Issue(3) :153-155.DOI:10.19768/j.cnki.dgjs.2024.03.041

6/10kV配电线路防雷分析及应用

Analysis and Application of Lightning Protection for 6/10 kV Distribution Line

刘彦生 王勇焕 李林卿
电工技术2024,Issue(3) :153-155.DOI:10.19768/j.cnki.dgjs.2024.03.041

6/10kV配电线路防雷分析及应用

Analysis and Application of Lightning Protection for 6/10 kV Distribution Line

刘彦生 1王勇焕 1李林卿1
扫码查看

作者信息

  • 1. 中国石化集团河南石油勘探局有限公司水电厂,河南 南阳 473132
  • 折叠

摘要

针对河南油田 6/10 kV配电线路雷击跳闸情况,进行雷击过电压分析,得出雷击跳闸的主要原因为建弧率过高.由 6/10 kV配电线路不同绝缘子配置方案下的雷击过电压的仿真计算结果可知,采用"一针两棒"绝缘子优化方案可使建弧率大幅降低,方案效果显著.

Abstract

This paper analyzes lightning overvoltage of a 6/10 kV distribution line in Henan Oilfield which encountered lightning trip,and determines main cause of lightning trip as the excessive arcing rate.Simulative calculation on lightning overvoltage under different insulator configuration schemes show that the adoption of'one pin,two rods'optimized scheme for insulators can achieve satisfactory result in 6/10 kV distribution lines,i.e.,significant reduction of arcing rate.

关键词

直击雷/感应雷/雷击跳闸/建弧率/绝缘子

Key words

direct lightning strike/induction lightning/lightning trip/arc building rate/insulator