首页|断路器分合闸线圈烧毁的原因分析及改进方法研究

断路器分合闸线圈烧毁的原因分析及改进方法研究

扫码查看
针对断路器分合闸操作过程中线圈烧毁现象,从断路器操作机构以及控制回路工作原理着手,分析得出分合闸线圈烧毁的根本原因为线圈长时间带电.对此提出了多种改进方法,经过比对确定非接触测量为最优方法.该方法可以在不拆卸操作机构器件、不更改控制回路的条件下完成对分合闸线圈运行情况的监测与评估,实现实时保护及提前预测.
Cause Analysis and Improvement Method for Burning of Circuit Breaker Break-Open Coil
In view of the phenomenon of coil burning during break-open operation of circuit breakers,starting with circuit breakers'mechanism and control circuit working principle,it is analyzed that the root cause for burning of break-open coils is long-time charging operation.Several corresponding improvement methods are proposed.After comparison,it is determined that non-contact measurement is the best method,which can monitor and evaluate the operation of break-open coil without disassembling the mechanism device and without changing the control loop,and can enable real-time protec-tion and advance prediction the coils.

circuit breakerbreak-open coilburningnon-contact measurementcontrol loop

靳楠、张岩坡、邳浚哲、张韶光、张旭

展开 >

国网河北省电力有限公司超高压分公司,河北 石家庄 050071

断路器 分合闸线圈 烧毁 非接触测量 控制回路

2024

电工技术
重庆西南信息有限公司(原科技部西南信息中心)

电工技术

影响因子:0.177
ISSN:1002-1388
年,卷(期):2024.(6)
  • 15