Finite Element-based Optimization Design of Heat Dissipation Structure of Dry-type Transformers
This paper establishes a three-dimensional symmetric simulation model of an 800 kVA 10 kV dry-type trans-former using finite element method,through which a simulative calculation onthe temperature field and air fluid field dis-tribution of the transformer is performed. It also analyzes the influence of heat dissipation plates with different structural parameters on temperature rise of the transformer,providing support for thermal optimization of dry-type transformers.
thermal-fluid field simulationdry-type transformertemperature rise