首页|一起电缆故障后继电保护动作行为分析及改进

一起电缆故障后继电保护动作行为分析及改进

扫码查看
对某水电站10 kV厂用电电缆接头故障后继电保护动作行为进行了分析,介绍了保护装置接地零序电流采样错误、保护动作死区等问题的发现方法,以及调整电缆零序CT安装位置、优化10 kV母线进线断路器安装位置、增加带电显示装置等有效解决措施.
Analysis on Action Behavior of Protective Relay against an Actual Cable Failure and Countermeasures
This paper analyzes the action behavior of protective relay after an actual event of internal 10 kV electrical cable joint failure in a hydropower plant. It reports methods of observing the problems such as sampling errors of grounding ze-ro-sequence current of protective relays,protective action dead zone,etc. It also proposes effective countermeasures inclu-ding adjusting cable zero-sequence CT installation position,optimizing installation position of 10 kV bus incoming circuit breaker,and adding live display devices.

cable failureprotective actionaction dead zoneinstrument transformercircuit breaker

卢伟、贾同威、陈相宇

展开 >

雅砻江流域水电开发有限公司,四川 成都 610051

电缆故障 保护动作 动作死区 互感器 断路器

2024

电工技术
重庆西南信息有限公司(原科技部西南信息中心)

电工技术

影响因子:0.177
ISSN:1002-1388
年,卷(期):2024.(7)
  • 2