500kV主变异常跳闸的原因分析及处理

扫码查看
通过分析某电厂一起6 kV开关三相短路故障造成500 kV主变及高厂变差动速断保护误动作事故,探讨变压器在不同保护运算方式下,主变及高厂变差动速断保护整定值的优化方案,最后提出防止主变及高厂变差动速断保护误动的措施,以提高保护装置动作的选择性,同时也为以后类似问题的调查分析提供借鉴.
Cause Analysis and Handling of Abnormal Tripping of 500 kV Main Transformer
This paper focuses on a three-phase short circuit fault which was encountered by a 6 kV switch in an actual power plant and caused undesired action of the differential instantaneous trip relays of the 500 kV main transformer and the high voltage auxiliary transformer.It discusses the optimization scheme for parameter tuning of the differential instan-taneous trip relays of the main transformer and the high voltage auxiliary transformer with respect to different protection calculation methods.It also proposes measures to prevent undesired action of the differential instantaneous trip relays and to improve selectivity of relays'action.The paper provides useful information for coping with similar problems.

transformerdifferential instantaneous trip relaythree-phase short circuit

陈根、赖武

展开 >

中海福建燃气发电有限公司,福建 莆田 351100

变压器 差动速断保护 三相短路

2024

电工技术
重庆西南信息有限公司(原科技部西南信息中心)

电工技术

影响因子:0.177
ISSN:1002-1388
年,卷(期):2024.(16)