首页|一起220 kV GIS母联电流不平衡分析及建议

一起220 kV GIS母联电流不平衡分析及建议

扫码查看
针对 GIS在运行中发生三相电流不平衡的事故,对 GIS设备运行时三相电流波形进行分析,并进行 X光检测及设备解体检查,结果表明事故是由 GIS隔离开关设计缺陷、设备内部机械磨损导致隔离开关 B相分闸异常引起的.针对此问题,建议厂家从设计及安装工艺上进行改进,同时对目前运行设备加强监视,并缩短设备检修周期.
Analysis and Suggestion on a Case of Three-phase Current Imbalance Fault Encountered by a Bus-tie Breaker in 220 kV GIS System
This essay reports the handling and causal analysis with respect to a case of three-phase current imbalance fault encountered by an operating gas insulated switchgear(GIS).The analysis carried out was on GIS three-phase current waveform,and the examinations performed were X-ray inspections and equipment disassembly check.It could be conclu-ded that the three-phase current imbalance was caused by B-phase opening abnormality of the GIS disconnector which re-sulted from design defects and internal mechanical wear.To solve this issue,it is suggested that manufacturer should im-prove in the design and installation process,and users should closely monitor currently operating equipment and adopt more frequent equipment maintenance.

three-phase current imbalanceGISX-ray inspectionopening abnormality

王世涛、冉月、蔡旭斐、凌博文

展开 >

国网上海超高压公司,上海 200433

三相电流不平衡 气体绝缘组合电器 X光检测 分闸异常