首页|换流站500 kV断路器重击穿故障原因分析

换流站500 kV断路器重击穿故障原因分析

扫码查看
介绍了一起换流站500 kV交流滤波器断路器分闸时重击穿故障,通过解体检查、化学分析、电场仿真等手段进行原因分析,可知断口内固体微粒引起电场畸变,造成重击穿.
Analysis of Heavy Breakdown of 500 kV Circuit Breaker in Converter Station
In this paper,the heavy breakdown fault of a 500 kV AC filter breaker in a converter station is introduced.The fault was analyzed by means of disassembly inspection,chemical analysis and electric field simulation.The solid particles in the fracture caused electric field distortion and caused rebreakdown.

500 kV circuit breakersolid particleselectric field distortionheavy breakdown

沈润鹏、周凯峰、王明、王俊娜

展开 >

国网上海超高压公司,上海 200063

500 kV断路器 固体微粒 电场畸变 重击穿

2024

电工技术
重庆西南信息有限公司(原科技部西南信息中心)

电工技术

影响因子:0.177
ISSN:1002-1388
年,卷(期):2024.(z1)