首页|630 MW氢冷发电机氢气纯度下降的原因分析及处理

630 MW氢冷发电机氢气纯度下降的原因分析及处理

扫码查看
文章介绍了双流环密封油系统的工作原理,并针对沙洲电厂630 M W发电机氢气纯度异常下降的情况,分析了双流环系统发电机氢气纯度下降的原因,并制定了相应检查方案.经排查确认氢气纯度下降是由密封油压力调整不当,致使发电机密封瓦处空侧油大量窜至氢侧,氢侧密封油中的空气析出进入发电机内导致的.
Cause Analysis and Treatment on Hydrogen Purity Drop in the 630 MW Hydrogen-Cooled Generator
The paper introduces the working princi-ple of the double-flow ring sealing oil system,analyzes the cause of hydrogen purity drop in the double-flow ring system and formulates corresponding inspection plans,based on the abnormal drop in hydrogen purity in a 630MW generator at Shazhou Power Plant.After investigation,it is confirmed that the drop of hydrogen purity is caused by improper adjustment of the sealing oil pressure,leading to a large amount of air-side oil leak from the generator's sealing bushing to the hydrogen side,making the air from the hy-drogen-side sealing oil enter into inside of the generator.

hydrogen-cooled generatorhydrogen pu-rityhydrogen supplementpurification

徐峰

展开 >

张家港沙洲电力有限公司(215600)

氢冷发电机 氢气纯度 补氢 提纯

2024

电机技术
上海电气(集团)总公司

电机技术

影响因子:0.146
ISSN:1006-2807
年,卷(期):2024.(6)