Application and Effect Analysis of Gas Turbine Imported Air Cooling Technology in Power Plants
This article takes a certain gas steam combined cycle cogeneration unit as the research object,and explores the application scheme and effect of using lithium bromide refrigeration equipment to cool the gas turbine inlet.Research has shown that this technology can effectively reduce the intake temperature of the gas turbine,improve the power and efficiency of the gas turbine.The actual application results show that the average intake temperature decreases by 2.2℃,the combustion engine power increases by 3.05%,and the heat consumption decreases by 1.83%.At the same time,this scheme fully utilizes the remaining cooling capacity of the original lithium bromide refrigeration equipment,and has the characteristics of low investment and high returns.This study provides useful reference for gas turbine power plants to improve equipment utilization and economic benefits.
gas turbineintake coolinglithium bromideenergy efficiency improvementeconomic performance