首页|高压XLPE电缆缓冲层故障机理与检测技术研究

高压XLPE电缆缓冲层故障机理与检测技术研究

扫码查看
高压XLPE电缆缓冲层故障频发,严重影响电缆安全运行,引起了广泛关注.根据缓冲层烧蚀故障特征,分析了高压XLPE电缆缓冲层电场特性并进行了初步仿真研究,得出局部放电是导致缓冲层故障的直接原因.提出了几种理论上可行的缓冲层故障检测方法并进行了简单验证,其有效性还待后续进一步试验与研究.
Research on Fault Mechanism and Detection Technology of Buffer Layer in High Voltage XLPE Cables
The frequent occurrence of faults in the buffer layer of high voltage XLPE cables significantly affects their safe operation,attracting widespread attention.Based on the characteristics of buffer layer erosion faults,this study conducts an analysis of the electric field distribution in the buffer layer of high voltage XLPE cables and performs preliminary simulation studies.It is determined that partial discharge is the direct cause of buffer layer faults.Several theoretically feasible detection methods for buffer layer faults are proposed and subjected to initial validation,although their effectiveness requires further testing and research.

high voltage XLPE cablesbuffer layerfault mechanismelectric field distributionpartial dischargedetection technology

张斌斌、王平羽

展开 >

国网上海市电力公司电缆分公司,上海 200122

高压XLPE电缆 缓冲层 故障机理 电场分布 局部放电 检测技术

2024

电力与能源
上海市能源研究所,上海市电力公司,上海市工程热物理学会

电力与能源

影响因子:0.494
ISSN:2095-1256
年,卷(期):2024.45(4)