首页|一起油浸式电流互感器轻微冒顶异常试验解体分析

一起油浸式电流互感器轻微冒顶异常试验解体分析

扫码查看
介绍了一起 110 kV油浸式电流互感器轻微冒顶后处理过程,通过油色谱和介损试验分析发现内部出现故障,停电后予以解体检查,发现内部一次绕组绝缘纸局部老化并伴有发热放电和包扎工艺缺陷,为后续该类型设备运行维护提供参考.
Test Analysis of an Oil-immersed Current Transformer Failure
It introduces the maintenance process of a 110 kV oil-immersed current transformer after failure.Through oil chromatography and dielectric loss test,it was found that there was an in-ternal fault.The transformer was disassembled and inspected after the power off,it shows the inter-nal primary winding insulation paper was partially aged with heating discharge and wrapping defects.It also can provide reference for operation and maintenance for the similar equipment.

oil-immersed current transformerfailureoil spectrumdielectric lossanalysis

张宏、郭建

展开 >

国网冀北电力有限公司秦皇岛供电公司,河北 秦皇岛 066000

油浸式电流互感器 冒顶 油色谱 介损 解体分析

2024

电气防爆
南阳防爆电气研究所

电气防爆

影响因子:0.26
ISSN:1004-9118
年,卷(期):2024.(6)