Analysis of Influence Factors of Loss Power Measurement for Low-voltage Switchgear Assembly
The power loss of complete sets of equipment is large during operation,so research on the influence fac-tors of measuring the power loss of complete sets of equipment is of certain significance for improving the design,re-search and development and manufacturing level of energysaving complete sets of products. Taking the measuring box as the research object,the measurement and analysis of various influencing factors are carried out. The results show that when measuring the power loss of the complete set of equipment,the measurement should be carried out as close as posible to the input end of the complete set of equipment,and the measurement should be carried out af-ter the stable operation of the complete set of equipment. The influence of ambient temperature on the power loss of the complete set of equipment should be considered,and overload will increase the power loss of the complete set of equipment.
low-voltage switchgear assemblyloss poweroverloadambient temperature