洁净手术室新风湿度的优先控制设计
Design of priority control for fresh air humidity in clean operating room
罗林生1
作者信息
- 1. 福建省建筑设计研究院有限公司 福建福州 350001
- 折叠
摘要
分析某医院洁净手术室空调系统的设计,包括空调热湿负荷计算、送风量和新风量计算、手术室空气处理过程焓湿图分析等.经实际计算,表明洁净手术室夏季采用新风湿度优先控制,相比采用新风处理到室内焓值节能效果更好.同时,对洁净手术室内温湿度设定和冷热源设计进行探讨,表明手术室温湿度合理设定以及手术室冷热源合理设计,对手术室能耗影响显著.
Abstract
This paper presents the design of air conditioning system in a clean operating room of a hospital,including calculations of heat and humidity load of air conditioning,air supply and fresh air volume,and analysis of enthalpy-humidity chart of the air handling process of the operating room.through practical calculation,it shows that prioritizingfreshair humidity control of a clean operating room can achieve better energy-saving effects compared to treating fresh air to indoor air enthalpy value in summer.additionally,this paper discussesthe set-ting of temperature and humidity and the design of heating and cooling sources in the clean operating room,the reasonable setting of operat-ing room temperature and humidity,as well as the reasonable design of operating room cooling and heating sources,have a significant impact on operating room energy consumption,the reasonable setting of operating room temperature and humidity,as well as the reasonable desig-ning of operating room cooling and heating sources,have a significant impact on operating room energy consumption.
关键词
洁净手术室/净化空调系统/湿度优先控制/焓湿图/节能/冷热源设计Key words
Clean operating room/Clean air conditioning system/Humidity priority control/Psychrometric diagram/Energy saving/Heat-ing and cooling source design引用本文复制引用
出版年
2024