为降低数据中心(DC)冷却系统的能耗和水耗,在机械制冷和直接新风冷却的基础上提出了一类耦合天空辐射制冷(RSC)的DC冷却方案,并研究了相应的系统构型和运行策略,建立了相关的数学模型。将冷却方案模拟使用在位于西安的一个模块化的集装箱DC上,对其节能节水效果和环境经济效益进行了评估,还对冷却方案在中国10个典型城市的地区适应性进行了分析。结果表明:所提出的耦合冷却方案(CM)与机械制冷(MCM)相比,冷却系统节能减排率达到了 55%,与主流的新风加湿冷却(OAHM)相比提高了 5。2%,同时水耗降低了 18。7%;相比于MCM,CM在各城市的节能减排率在42。9%~78。1%之间,体现出良好的节能节水效益。
Analysis of Free Cooling Scheme Coupled With Radiative Sky Cooling in Data Center
In order to reduce the energy and water consumption of the cooling system in data center(DC),a DC cooling scheme coupled with radiative sky cooling(RSC)was proposed on the basis of mechanical cooling and direct air-side economizer,the corresponding system configuration and operation strategy were designed,and the mathematical model was established.A modular container DC in Xi'an coupled with the proposed scheme was simulated,and the energy and water saving effects as well as the environmental economic benefits were evaluated.In addition,the regional adaptability of the cooling scheme in 10 typical cities in China was analyzed.The results showed that,the energy saving and emission reduction rate of the proposed coupled cooling scheme(CM)can be attained 55%compared with the mechanical cooling(MCM),and increased by 5.2%compared with the outdoor air humidification scheme(OAHM).Meanwhile,the water consumption is reduced by 18.7%.Additionally,compared with MCM,the energy saving and emission reduction rate of CM in the studied 10 cities is between 42.9%and 78.1%,better energy saving and water saving benefits can be obtained.

data centerfree coolingair-side economizerradiative sky coolingenergy conserva-tion and emission reduction

文凯、王程远、王晓坡、赵攀、王江峰、何茂刚

展开 >

西安交通大学热流科学与工程教育部重点实验室,陕西 西安 710049

数据中心 自然冷却 新风冷却 天空辐射制冷 节能减排

国家自然科学基金重点项目陕西省自然科学基金

519360092020JM-020

2024

工程热物理学报
中国工程热物理学会 中国科学院工程热物理研究所

工程热物理学报

CSTPCD北大核心
影响因子:0.4
ISSN:0253-231X
年,卷(期):2024.45(5)
  • 20