Analysis of Free Cooling Scheme Coupled With Radiative Sky Cooling in Data Center
In order to reduce the energy and water consumption of the cooling system in data center(DC),a DC cooling scheme coupled with radiative sky cooling(RSC)was proposed on the basis of mechanical cooling and direct air-side economizer,the corresponding system configuration and operation strategy were designed,and the mathematical model was established.A modular container DC in Xi'an coupled with the proposed scheme was simulated,and the energy and water saving effects as well as the environmental economic benefits were evaluated.In addition,the regional adaptability of the cooling scheme in 10 typical cities in China was analyzed.The results showed that,the energy saving and emission reduction rate of the proposed coupled cooling scheme(CM)can be attained 55%compared with the mechanical cooling(MCM),and increased by 5.2%compared with the outdoor air humidification scheme(OAHM).Meanwhile,the water consumption is reduced by 18.7%.Additionally,compared with MCM,the energy saving and emission reduction rate of CM in the studied 10 cities is between 42.9%and 78.1%,better energy saving and water saving benefits can be obtained.
data centerfree coolingair-side economizerradiative sky coolingenergy conserva-tion and emission reduction