广东电力2024,Vol.37Issue(1) :94-101.DOI:10.3969/j.issn.1007-290X.2024.01.011

基于数字孪生的GIS外部局部放电干扰识别

Identification of External Partial Discharge Interference in GIS Based on Digital Twin Technology

方义治 林钰灵 梁育雄 吴伟文 姜志彬 沈道义 易孝波
广东电力2024,Vol.37Issue(1) :94-101.DOI:10.3969/j.issn.1007-290X.2024.01.011

基于数字孪生的GIS外部局部放电干扰识别

Identification of External Partial Discharge Interference in GIS Based on Digital Twin Technology

方义治 1林钰灵 1梁育雄 1吴伟文 1姜志彬 1沈道义 2易孝波3
扫码查看

作者信息

  • 1. 南方电网广东珠海供电局,广东珠海 519000
  • 2. 上海格鲁布科技有限公司,上海 201210
  • 3. 珠海市伊特高科技有限公司,广东珠海 519000
  • 折叠

摘要

在实际的变电站复杂环境中,除了来自环境噪声的影响外,气体绝缘金属封闭开关设备(gas insulated switchgear,GIS)在线监测系统还会受到外部局部放电信号的干扰.针对目前GIS局部放电在线监测系统无法识别外部局部放电信号的缺陷,结合数字孪生技术的优势,开展GIS外部局部放电干扰识别研究,提出一种基于数字孪生的GIS外部局部放电干扰识别机制,建立GIS数字孪生整体模型和信号衰减部件模型,分析特高频信号衰减速率.根据衰减速率对比,完成外部局部放电信号识别,并通过仿真实验验证该算法的有效性.

Abstract

In the complex environment of actual substations,in addition to the impact of environmental noise,the gas insulated switchgear(GIS)online monitoring system also receives interference from external partial discharge(PD)signals.To address the current defect that GIS PD online monitoring systems can't identify external PD signals,this paper conduct research on the identification of external PD interference in the GIS,combining the advantages of digital twin technology.It proposes a mechanism for identifying external PD interference in the GIS based on digital twins,establishes an overall digital twin model of the GIS and a signal attenuation component model,and analyzes the ultra-high frequency signal attenuation rate.According to attenuation rate comparisons,it completes the identification of external PD signals,and verifies the effectiveness of the algorithm proposed through simulation experiments.

关键词

数字孪生/抗干扰技术/局部放电/目标识别

Key words

digital twin/anti-interference technology/partial discharge/target identification

引用本文复制引用

基金项目

中国南方电网有限责任公司科技项目(030400KK52220033GDKJXM20220875)

出版年

2024
广东电力
广东电网公司电力科学研究院,广东省电机工程学会

广东电力

CSTPCD北大核心
影响因子:0.527
ISSN:1007-290X
参考文献量20
段落导航相关论文