首页|换流变压器铁心夹件接地电流谐波特性分析

换流变压器铁心夹件接地电流谐波特性分析

扫码查看
为了解决仅依据接地电流的全电流值无法准确有效判断换流变压器的检修状态问题,以及更深入探究换流变压器铁心、夹件接地电流的特性,采用汉宁窗插值快速傅里叶变换算法对采样信号进行谐波分析,得到接地电流基波和2~50次谐波的幅值及含有率.对比分析基波与全电流的变化趋势,以及不同时刻接地电流的全电流、基波、谐波数据,得到谐波幅值变化幅度,进一步揭示换流变压器铁心、夹件接地电流值过大和跳动的问题,为判断换流变压器铁心、夹件接地电流状态与变压器运行状况提供新的思路.
Analysis on Harmonic Characteristics of Grounding Current of Converter Transformer Core Clamp
In order to solve the problem that the full current value of the grounding current can't accurately and effectively determine the maintenance status of the converter transformer,and further explore the characteristics of the grounding current of the core clamp of the converter transformer,this paper uses Hanning window interpolation and fast Fourier transform(FFT)algorithms to analyze the original sampling signals of the grounding current of the core clamp,and obtain the amplitudes and contents of the fundamental wave and 2~50 harmonics of the grounding current.It compares the change trends of the fundamental current and the full current,as well as the harmonic data of the grounding current at different times.It also obtains the change amplitude of the harmonic,which further reveals the problem of excessive and jumping of the grounding current value of the converter transformer core clamp and provides a new idea for determining the grounding current status of the core clamp of the converter transformer and the operation status of the transformer.

converter transformercore clampharmonicgrounding currentfundamental wave

苗彭、王启斌、武文杰、占南、林枫

展开 >

长园共创监测技术(南京)有限公司,江苏 南京 210003

江苏师范大学 科文学院,江苏 徐州 221116

换流变压器 铁心夹件 谐波 接地电流 基波

国家电网山东省电力公司电力科学研究院自主研发项目

ZY-2022-08

2024

广东电力
广东电网公司电力科学研究院,广东省电机工程学会

广东电力

CSTPCD北大核心
影响因子:0.527
ISSN:1007-290X
年,卷(期):2024.37(3)
  • 21