首页|基于激光吸收光谱的CO/CO2/H2S浓度同步在线测量研究

基于激光吸收光谱的CO/CO2/H2S浓度同步在线测量研究

扫码查看
CO、CO2、H2S是燃煤锅炉炉内气氛重要组成部分,其浓度不仅能够反映燃烧工况,还可作为水冷壁高温腐蚀程度判断依据,因此实现CO、CO2、H2S浓度的准确测量意义重大.首先采用波长调制-直接吸收(WM-DAS)方法结合约40 m长光程Herriott池,在室温低压下,开展不同CO/CO2浓度配比下三种气体吸收率同步测量实验,结果表明三种气体的吸收率测量值与理论计算值相近,相对误差在6.82%以内,测量结果可靠性较高;然后对不同浓度CO/CO2(0~2 000 μL·L-1)、H2S(0~20 μL·L-1)进行动态测量,结果表明,测量系统对三种组分浓度变化的响应具有较好的线性度.
On Line Simultaneous Measurement of CO/CO2/H2S Concentration Based on Laser Absorption Spectrum
CO,CO2 and H2S are important components of the atmosphere in the coal-fired boiler.Their concentrations can not only reflect the combustion conditions but also serve as the basis for judging the high-temperature corrosion degree of the water wall.Therefore,it is of great significance to measure the concentrations of CO,CO2,and H2S accurately.In this work,the WM-DAS method and Herriott cell with a length of about 40 m were used to carry out synchronous measurement of three kinds of gasabsorptivity under different CO/CO2 concentration ratios at room temperature and low pressure.The results showed that the measured values of the absorptivity of the three gases agree very well with the theoretical calculation values,and the relative error is within 6.82%,which suggests the highly reliable of this method.Subsequently,the dynamic measurement of CO/CO2(0~2 000 μL·L-1)and H2S(0~20 μL·L-1)was carried out.The results showed that the measurement system has good linearity in response to the concentration changes of the three components.

Wavelength modulation-direct absorption spectroscopyCO concentrationCO2 concentrationH2S concentrationSimultaneous measurement

张学军、陈勤根、杨展、邓琴、贺拴玲、彭志敏

展开 >

浙江浙能中煤舟山煤电有限责任公司,浙江舟山 310007

浙江浙能技术研究院有限公司,浙江杭州 310015

清华大学能源与动力工程系,电力系统与发电设备控制与仿真国家重点实验室,北京 100084

波长调制-直接吸收光谱 CO浓度 CO2浓度 H2S浓度 同步测量

国家自然科学基金国家重点研发计划

119722132019YFB20060002

2024

光谱学与光谱分析
中国光学学会

光谱学与光谱分析

CSTPCD北大核心
影响因子:0.897
ISSN:1000-0593
年,卷(期):2024.44(5)