甘肃科学学报2024,Vol.36Issue(6) :30-36.DOI:10.16468/j.cnki.issn1004-0366.2024.06.006

考虑节点域影响的钢管约束钢筋混凝土柱框架结构抗震性能研究

Research on seismic performance of steel tubed reinforced concrete column frame structures considering the influence of joint region

赵航 郑宣宣 张玉洁 李窍 陈黄健
甘肃科学学报2024,Vol.36Issue(6) :30-36.DOI:10.16468/j.cnki.issn1004-0366.2024.06.006

考虑节点域影响的钢管约束钢筋混凝土柱框架结构抗震性能研究

Research on seismic performance of steel tubed reinforced concrete column frame structures considering the influence of joint region

赵航 1郑宣宣 1张玉洁 1李窍 2陈黄健3
扫码查看

作者信息

  • 1. 陕西工业职业技术学院土木工程学院,陕西咸阳 712000
  • 2. 山东省建筑科学研究院有限公司,山东济南 250000
  • 3. 中国建筑一局(集团)有限公司,北京 100161
  • 折叠

摘要

近年来,钢管约束钢筋混凝土(STRC)柱结构已成为组合结构研究热点之一.约束钢管在柱端断开能够充分发挥其对混凝土的约束效果,增强柱体承载力及抗震性能.然而,节点区域将变得相对薄弱,传统结构体系性能分析中多以节点为刚性域,不考虑节点本身的变形及受损对结构的影响,这将导致STRC柱结构分析及设计存在一定的安全隐患.本文在STRC框架结构中引入节点单元Joint2D来模拟节点的受荷变形全过程,对比分析了节点单元对抗震性能模拟结果的影响,评价了不同强节点系数结构的地震易损性和抗倒塌性能.结果表明,不考虑节点性能的分析结果过高地估计了结构性能,造成不满足规范限值要求的性能指标被分析为满足要求.《钢管约束混凝土结构技术标准》中一级抗震的强节点系数1.5在罕遇地震时将偏于不安全,为满足结构使用安全及抗倒塌能力,建议取强节点系数为1.7.

Abstract

In recent years,steel tubed reinforced concrete(STRC)column structures have become one of the research hotspots in composite structures.The disconnection of the steel tube at the end of the column could fully exerts its confinement effect on core concrete,enhancing the bearing capacity and seismic per-formance of the column.However,the joint region will become relatively weak.When conducting structural performance analysis traditionally,joints are often regarded as rigid region,without considering the deform-ation and damage of the joints on the structure.This will cause certain safety hazards in the analysis and de-sign of STRC column structures.This article utilizes the joint element Joint2D to simulate the entire process of joint deformation in the STRC frame structure,analyzes the influence of joint elements on seis-mic performance simulation results,as well as the seismic vulnerability evaluation and collapse resistance performance of structures with different strong joint coefficients.The results indicate that the analysis re-sults without considering joint performance will overestimate the structural performance,resulting in per-formance indicators that do not meet the code limit requirements being analyzed as meeting the require-ments.The strong joint coefficient 1.5 for the first level seismic resistance in the code Technical Standard for Steel Tube Confined Concrete Structures will tend to be unsafe in rare earthquakes.To meet the safety and collapse resistance of the structure,it is recommended to take a strong joint coefficient of 1.7.

关键词

钢管约束钢筋混凝土柱框架/节点域单元/抗震性能/易损性

Key words

Steel tubed reinforced concrete column frame structure/Joint element/Seismic performance/Structure vulnerability

引用本文复制引用

出版年

2024
甘肃科学学报
甘肃省科学院 中国科学院资源环境科学信息中心

甘肃科学学报

CSTPCD
影响因子:0.414
ISSN:1004-0366
段落导航相关论文