Typical Fault Analysis Caused by Shielded Separable Connector
As for the typical fault due to the shielded separable connector in this paper,the cause of the fault is ana-lyzed comprehensively from the product structure and picture of the faulty object and the reason for the fault is pro-posed.The rationality of the fault analysis is indicated by way of modeling and electric filed simulation analysis of the epoxy resin and inserts of the shielded separable connector under different coordination conditions.According to rele-vant standards,the correctness of the fault analysis is proved further through comparison and test of partial discharge under such insulation fault condition and normal condition.The guidance suggestion to avoid the occurrence of such insulation fault is proposed in combination with the fault characteristics.
separable connectorinsulatorfault analysiselectric field simulationpartial discharge