首页|杆塔分流对冲击接地电阻测量的影响分析

杆塔分流对冲击接地电阻测量的影响分析

扫码查看
杆塔的冲击接地电阻是衡量其雷电防护性能的重要参数,目前国内外大量的研究工作主要集中在冲击接地电阻的电路等效和理论计算上,且在各种分析方法上并未达成一致意见,而在冲击接地电阻的实际现场测量方面的研究工作较少.本文主要采用仿真结合小模型实测的方法研究了在冲击接地电阻实测时电流的准确测量问题,提出并验证了杆塔分流对于实测时电流的影响,并全面分析了杆塔分流系数相关的各个影响因素,在此基础上提出了一种精确的电流修正方法.
Impacts of Tower Current Shunting on Impulse Earthing Resistance Measurement
The impulse earthing resistance is an important parameter to measure the lightning protection performance of transmission towers.Nowadays,the current study at home and abroad mainly focuses on its circuit equivalence and theoretical calculation,and the various analysis methods haven't reached consensus.There has been relatively less study on practical field measurement of impulse resistance.In this paper,the accurate current measurement in measuring impulse resistance is studied using simulation and small-scale model measuring; the impacts of tower current shunting on current measurement are proposed and verified; each influencing factor of tower current shunting is comprehensively analyzed and thereupon an accurate current correcting method is put forward.

impulse earthing resistanceshunting coefficientpeak delay coefficientcurrent correction

夏雨、马经纬、傅正财、李锐海

展开 >

上海交通大学电气工程系,电力传输与功率变换控制教育部重点实验室,上海200240

特高压工程技术(昆明、广州)国家工程实验室,广州510080

冲击接地电阻 分流系数 峰值延时系数 电流修正

特高压工程技术(昆明、广州)国家工程实验室开放基金

NEL201310

2014

华东电力
华东电力试验研究院有限公司

华东电力

CSTPCD
影响因子:0.551
ISSN:1001-9529
年,卷(期):2014.42(2)
  • 7
  • 13