Distribution Network Reverse Power Protection for Distributed Garbage Incineration Power Plant
This paper summarizes the status of distributed garbage incineration power generation and the requirements for grid integration,emphatically the reverse power protection.When distributed power is designed as the irreversible access to the distribution power grid,if the detected reverse current exceeds a certain value,the distributed power and distribution network will be disconnected,so reverse power protection device is indispensable in the distributed power access.The 17th outlet waste incineration power plant of Shanghai Jiading 35kV Zhuqiao Station was set as an example to study the reverse power protection applications in distributed garbage incineration power plant access to power grid.
distributed garbage incineration power plantdistribution networkreverse power protection