首页|NETOMAC程序与BPA程序在电力系统计算分析中的比较研究

NETOMAC程序与BPA程序在电力系统计算分析中的比较研究

扫码查看
对电力系统计算分析的两个程序NETOMAC和BPA进行了综合的比较研究.以IEEE 9节点系统为算例,分别针对潮流计算功能和暂态稳定计算功能进行了NETOMAC程序与BPA程序的比较研究;以包括上海、江苏、浙江、安徽、福建在内的华东电网全网某年度网架系统为算例,针对小干扰稳定计算分析功能进行了NETOMAC程序与BPA程序的比较研究.研究表明,对于潮流计算两个程序结果完全一致;对于不同发电机模型和不同负荷模型的暂态稳定计算,两个程序结果都能较好地吻合;对于华东全网的小干扰稳定计算分析,两个程序的结论基本一致.
Comparative Study of NETOMAC and BPA in Power System Analysis
This paper makes a comprehensive comparative study between NETOMAC and BPA,two power system calculation and analysis programs.With IEEE 9 nodes system as example,NETOMAC and BPA are compared respectively in terms of power flow calculation and transient stability calculation function; with East China Power Grid (including Shanghai,Jiangsu,Zhejiang,Anhui,Fujian) as example,cut some year rack system for example,comparison is made in view of their small signal stability analysis function.Study shows that their power flow calculation results are identical; their transient stability calculation results for different generator models and load models can be matching; their small signal stability analysis results of East China Power Grid are basically identical.

power systemNETOMACBPAload flowtransient stabilitysmall disturbance

赵学强

展开 >

国网上海市电力公司电力科学研究院,上海200437

电力系统 NETOMAC BPA 潮流 暂态稳定 小干扰

2014

华东电力
华东电力试验研究院有限公司

华东电力

CSTPCD
影响因子:0.551
ISSN:1001-9529
年,卷(期):2014.42(8)
  • 1
  • 2