首页|300 MW发电机转子匝间短路故障分析与处理

300 MW发电机转子匝间短路故障分析与处理

扫码查看
介绍一起300 MW汽轮发电机启动过程中转子发生匝间短路的故障,结合转子匝间短路后运行参数的变化情况、转子现场试验检查判断情况和转子返厂解体后故障点的检查情况,从发电机转子端部设计结构、转子绕组塑性变形等方面进行分析,认为转子端部结构不能满足机组日常深度调峰的运行工况是导致故障的根本原因,并提出对端部结构进行改进优化的处理和防范措施.
Analysis and Treatment of Interturn Short Circuit Fault in 300 MW Generator Rotors
This article introduces an incident where a 300 MW steam turbine generator experienced a rotor interturn short circuit fault during the start-up process.It combines the analysis of changes in operational parameters after the rotor interturn short circuit,on-site rotor test inspections and evaluations,and inspections of fault points after the rotor is returned for disassembly.The analysis focuses on aspects such as the design structure of the generator rotor end,plastic deformation of rotor windings,and concludes that the rotor end structure fails to meet the operational demands of deep peaking cycles,which is the root cause of the fault.Recommendations are made for improving and optimizing the end structure design,along with preventive measures.

generatorrotorinterturn short circuitdeep peak shaving

张寒

展开 >

国家能源集团三河发电有限责任公司,河北 三河 065201

发电机 转子 匝间短路 深度调峰

2024

河北电力技术
河北省电机工程学会,河北省电力研究院

河北电力技术

影响因子:0.306
ISSN:1001-9898
年,卷(期):2024.43(4)
  • 2