Year-round Refrigeration System Cooling Tower Antifloc Study
During the operation of information equipment in the information data room,a large amount of heat is generated.In order to ensure the temperature and humidity environment of the room and ensure the safety of information equipment operation,a year-round refrigeration system is usually designed to provide cold source supply for the terminal information room.In Beijing,March May is the"floating floc"season every year.A large number of poplar and willow flocs are easily sucked into the cooling tower for circulation,leading to a"no water flow"shutdown failure of the chiller unit,affecting the energy supply of the system.In severe cases,it may lead to equipment overheating and data loss in the terminal information room.Therefore,this article takes the annual refrigeration system of Beijing Daxing International Airport Information Center ITC as an example to conduct a series of research on the anti flocculation device of the cooling tower,develop a three-dimensional anti flocculation device,and conduct experimental research on the balance relationship between the protection effect and the impact of air volume,achieving the best anti flocculation effect.
data roomannual refrigeration systemcooling toweranti flocculentDaxing Airport