核辅助厂房通风系统(DVN)是保障辐射防护屏障的最后一个环节,通过其负压控制来保证辐射防护屏障的完整性和稳定性.运行实践中发现,在执行一本关于DVN的负压调整的实验规程时发现8DVN018LP读数不稳定且超过规程中的限值.作者从DVN系统负压控制的原理出发,分析了 8DVN018LP读数不稳定且超过规程中的限值的根本原因,提出了增加规程中限值的合理区间,为之后顺利实施对DVN系统负压监测提供方案.
Analysis and Improvement of Negative Pressure Problems in DVN System
DVN system is the last link to protect the radiation protection barrier,through its negative pressure control to ensure the integrity and stability of the radiation protection barrier.In practice,it was found that the 8DVN018LP readings were found to be unstable and exceeded the limits in the protocol when performing a test procedure on the negative pressure adjustment of DVN.Based on the principle of negative pressure control of DVN system,the author analyzes the fundamental reason that the 8DVN018LP reading is unstable and exceeds the limit value in the program,and puts forward the reasonable interval to increase the limit value of the program,and then provides the negative pressure monitoring for DVN system Program.