一起35 kV线路两基相邻直线杆玻璃绝缘子串的多点故障分析

A Multipoint Fault Analysis for Glass Insulator String on Two Adjacent Straight-Line Poles of 35 kV Transmission Line

郑江 刘均华 卓少伟
红水河2024,Vol.43Issue(5) :122-127,145.DOI:10.3969/j.issn.1001-408X.2024.05.023

一起35 kV线路两基相邻直线杆玻璃绝缘子串的多点故障分析

A Multipoint Fault Analysis for Glass Insulator String on Two Adjacent Straight-Line Poles of 35 kV Transmission Line

郑江 1刘均华 2卓少伟3
扫码查看

作者信息

  • 1. 广西大学电气工程学院,广西 南宁 530004
  • 2. 广西电网有限责任公司防城港供电局,广西 防城港 538004
  • 3. 广西电网有限责任公司崇左供电局,广西 崇左 532399
  • 折叠

摘要

针对一起 35 kV线路两基相邻直线杆玻璃绝缘子串的残锤、雨闪、电弧风偏及断线等的多点故障,笔者分析了故障原因,并提出改进措施.结果表明:该线路 19 号杆仅有 2 片绝缘子、1 个残锤的A相 2 片串发生持续间歇雨闪,扣除残锤后绝缘子的每串最少片数少于规范要求值、单相雨闪故障延时跳闸等是引发该起故障的主要原因;35 kV线路采用 4 片玻璃绝缘子串或改用复合绝缘子,加强绝缘子串的可恢复绝缘、抗污及灭弧性能,可防止发生此类故障.

Abstract

In view of a multipoint fault of residual hammer,rain flashover,arc wind deviation and broken line of glass insulator string on two adjacent straight-line poles of 35 kV transmission line,the causes of the fault are analyzed,and improvement measures are put forward.The results showed that only two insulators and one residual hammer in the A-phase two-piece string of the 19th pole of the line experienced continuous intermittent rain flashes,the minimum number of insulators per string is less than the required value in the specifications after deducting the residual hammer,and the delay tripping of single-phase rain flashover fault is the main cause of the fault;The 35 kV line adopts four glass insulator strings or uses composite insulators to enhance the recoverable insulation,anti-pollution and arc extinguishing performance of the insulator strings,which can prevent such faults from occurring.

关键词

35/kV线路/玻璃绝缘子/残锤/故障分析/间歇雨闪/间歇过电压/复合绝缘子

Key words

35 kV transmission line/glass insulator/residual hammer/fault analysis/intermittent rain flashes/intermittent overvoltage/composite insulator