Exploration of the adaptability and energy-saving potential of communication room ventilation and cooling system based on air purification technology
By analyzing the characteristics of communication rooms and the current state of air conditioning energy consumption,a ventilation and cooling system based on air purification technology is proposed.Taking a communication room in Qingdao as an example,the indoor air cleanliness after the application of the ventilation and cooling system is tested on-site.The energy consumption of the room is quantitatively simulated and analyzed using the DeST software,and the annual energy saving rate after the application of the ventilation and cooling system is calculated.Calculations are also conducted for typical cities in five climatic zones to explore the energy-saving potential of the ventilation and cooling system in the five major building thermal zones across the country.The results show that after applying the ventilation and cooling system,the energy saving rate of a certain room in Qingdao is 64.95%,and the simulated energy saving rate of the ventilation and cooling system nationwide is between 33.37%and 73.7%.The energy-saving effect of applying the ventilation and cooling system in communication rooms is very significant.
communication roomventilation and cooling systemenergy-saving potential