洁净与空调技术2024,Issue(1) :28-33.

水冷多联管热管系统的有限时间热力学分析与优化

Finite time thermodynamic analysis and optimization of water cooled multi-spilit heat pipe system(MSHPS)

杨志新 陈飞虎 刘杰宏 徐寒婷
洁净与空调技术2024,Issue(1) :28-33.

水冷多联管热管系统的有限时间热力学分析与优化

Finite time thermodynamic analysis and optimization of water cooled multi-spilit heat pipe system(MSHPS)

杨志新 1陈飞虎 1刘杰宏 1徐寒婷1
扫码查看

作者信息

  • 1. 长沙麦融高科股份有限公司
  • 折叠

摘要

采用有限时间热力学、㶲方法分析了水冷多联热管系统(MSHPS).计算结果表明,IT服务器应该集中安排在1.3m以下的位置.CDU在6s的时间内具有约74 J的传热量.最佳流量时CDU的速率为0.82kg/s.计算了免费冷却时间,部分免费冷却时间.并分析了中国主要城市的节能潜力从61%到25%.研究结果对其他管网系统实际应用具有重要意义.

Abstract

The finite time thermodynamic analysis,the exergy method were employed to build the simulation model of the combined system of water cooled multi-spilit heat pipe system(MSHPS)used in data center.The results show that the IT servers should concentrate on arranging at the location below 1.3 m.The CDU has a heat transfer of about 74 J in a period of 6 s.And the optimum flow rate of the CDU is 0.82 kg/s.Then the free cooling time,part time free cooling and energy saving potential in major cities of China were analysised.The energy saving potential is from 61%to 25%.The results are of great significance for the operational control and practical application of other pipe-net systems.

关键词

有限时间热力学分析/数据中心/热管空调系统/制冷剂流量分布特性/节能潜力

Key words

Finite time thermodynamic analysis/Exergy method/IDC room/Heat pipe air-conditioning system/SIMULINK software/Refrigerant flow distribute characteristic/Energy saving potential