首页|优质水源条件下臭氧生物活性炭工艺运行模式探讨

优质水源条件下臭氧生物活性炭工艺运行模式探讨

扫码查看
针对水厂引入优质水源后如何管理好臭氧生物活性炭工艺(O3-BAC),降低生产能耗的问题,以确保水质安全、设备设施可靠的前提下,在J和N水厂分别开展停用和小流量运行O3-BAC的生产性试验,重点分析了停用O3-BAC对水处理效果、炭滤池和重点设备的影响,并对小流量运行O3-BAC的运行模式进行了初探讨.结果表明,在原水为优质水源的条件下,若停用O3-BAC,常规工艺处理高pH原水时,出厂铝会升高;炭池停用45 d内,滤料上微生物活性急剧下降,重启运行后65 d后仅恢复至停用前的64%;炭池停用再启动后,出水氨(以N计)含量呈现先增长后下降,且增长量随停用时间延长而增大,最高可升至0.7 mg/L,24小时后达到稳定;停用时间小于6个月,提升泵等重点设备性能无明显变化.若采用小流量运行O3-BAC(超越水量约60%),N水厂电耗和氧耗分别下降8.80%和28.72%.
Discussion on the operating mode of ozone biological activated carbon process under the high-quality water source
In response to the issue of how to manage the ozone biological activated carbon(O3-BAC)process well and reduce energy consumption in water plant production after introducing high-quality raw water in water plants,under the premise of ensuring treatment water quality safety and reliable equipment and facilities,production experiments were conducted on the O3-BAC for de-commissioning and low flow operation at J and N water plants,with a focus on analyzing the im-pact of stopping O3-BAC on water treatment efficiency,carbon filters,and key equipment.Prelim-inary discussions were also conducted on the operation of O3-BAC at low flow rates.The results indicate that under the condition that the raw water is a high-quality water source,if O3-BAC is stopped,the aluminum content in the treatment water will increase when the conventional treat-ment is used to treat high pH raw water.Within 45 days of deactivation of carbon filter,the micro-bial activity on the filter material sharply decreased,and after 65 days of restart,it only recovered to 64%of the level before deactivation.After the carbon filter is restarted,the ammonia content in effluent(measured as N)shows a increase followed by a decrease,and the growth increases with the extension of stop time,reaching a maximum of 0.7 mg/L,and stable after 24 hours.The downtime is less than 6 months,and there is no significant change in the performance of key equip-ment such as intermediate lifting pumps.If O3-BAC is operated at low flow rate(exceeding water by about 60%),the electricity and oxygen consumption of N water plant have decreased by 8.80%and 28.72%respectively.

High-quality water sourceReduce energy consumptionOperating modeMicrobial activityOperation of O3-BAC at low flow rates

郭红峰、王佳函、张嘉恩、方榕华、叶逸之、查正林

展开 >

杭州市水务集团有限公司,杭州 310012

中国联合工程有限公司,杭州 310051

优质水源 降低能耗 运行模式 微生物活性 小流量运行O3-BAC

2024

给水排水
亚太建设科技信息研究院,中国建筑设计研究院,中国土木工程学会

给水排水

CSTPCD北大核心
影响因子:0.8
ISSN:1002-8471
年,卷(期):2024.50(10)