Simulation of Thermal Environment and Waste Heat Recovery Performance of High Radiant Heat Plant
In order to solve the problems of high radiant heat workshop temperature,poor working environment and serious waste heat loss,the effect of heat absorption screen under different water flow conditions in the waste heat recovery and reduction of workshop temperature was analyzed by using FLUENT software through the optimized heat absorption screen model,and the results showed that the average indoor temperature dropped from 40.18 ℃ to 32.51 ℃ after adding the heat absorbing screen,which had a certain cooling effect.When the water flow rate is 0.025 kg/s,the waste heat recovery efficiency is 56%,and the heat recovery effect is obvious.The research results realize that low-quality waste heat is used for social heating and also improve the thermal environment of high-radiant heat workshop,which is of great significance for improving the comprehensive competitiveness of industrial enterprises and achieving social and economic benefits.