建筑钢结构进展2024,Vol.26Issue(12) :1-11.DOI:10.13969/j.cnki.cn31-1893.2024.12.001

波形腹板部分包覆组合柱弱轴方向偏心受压试验研究

Eccentric Compression Test of Partially Encased Composite Columns with Corrugated Webs Around Weak Axis

王威 包海洋 白淙尤 刘磊 陈乐乐
建筑钢结构进展2024,Vol.26Issue(12) :1-11.DOI:10.13969/j.cnki.cn31-1893.2024.12.001

波形腹板部分包覆组合柱弱轴方向偏心受压试验研究

Eccentric Compression Test of Partially Encased Composite Columns with Corrugated Webs Around Weak Axis

王威 1包海洋 1白淙尤 1刘磊 1陈乐乐1
扫码查看

作者信息

  • 1. 西安建筑科技大学 土木工程学院,西安 710055
  • 折叠

摘要

针对传统部分包覆组合柱(PEC柱)中腹板易变形屈曲,以及与混凝土协同作用较弱、易分离等问题,提出一种将腹板形式由平钢板改为波形钢板的波形腹板PEC柱.考虑强弱轴方向、波形腹板方向、横向系杆间距、偏心距4个关键因素,设计10个波形腹板PEC柱试件并进行偏心加载试验.试验结果表明:波形腹板PEC柱试件在偏心受压下的破坏形态基本一致,均表现为受压侧翼缘鼓曲变形和混凝土压碎失效.试件在强轴方向的承载力较弱轴方向的承载力最大增幅为61.20%,延性最大增幅为63.06%;竖向波形腹板试件的承载力和初始刚度均高于横向波形腹板试件的相应值;较小偏心受压试件的承载力高于较大偏心受压试件的承载力;减小横向系杆间距,试件达到峰值荷载后的延性性能提高,最大增幅为 75.16%.通过有限元软件ABAQUS建立波形腹板PEC柱偏心受压模型,在与试验结果进行对比验证的基础上,结合已有PEC柱试件的相关规范,拟合得到竖向波形腹板PEC柱压弯承载力计算公式,且理论值与试验值的差异在10%以内.

Abstract

In order to solve the problems of traditional partially encased composite columns(PEC columns),including easy deformation and buckling of webs,weak synergistic effect with concrete,and easy separation,corrugated web PEC column with corrugated steel plate instead of flat steel plate was proposed.Considering four key factors:strong and weak axis direction,corrugated web direction,transverse tie bar spacing and eccentricity,ten corrugated web PEC column specimens were designed,and eccentric loading experiments were carried out.The test results show that the failure modes of PEC columns with corrugated webs under eccentric compression are the same,manifested as bulging deformation of compression side flange and crushing failure of concrete.Compared to the specimen around weak axis,the bearing capacity and ductility of the specimen around strong axis can be increased by 61.20%and 63.06%at most,respectively;the bearing capacity and initial stiffness of vertical corrugated web specimens are higher than those of transverse corrugated web specimens;the bearing capacity of the specimen with smaller eccentricity is higher than that of the specimen with larger eccentricity;by reducing the spacing of transverse tie bars,the ductility of the specimen can be improved by 75.16%at most after reaching the peak load.The eccentric compression model of the corrugated web PEC column was established by ABAQUS finite element software.The formula for calculating the eccentric bearing capacity of vertical corrugated web PEC column is fitted based on comparing the test results and combining the existing relevant specifications for PEC column.The difference between the theoretical and experimental value is within 10%.

关键词

波形腹板/部分包覆组合柱/偏心受压试验/有限元模拟/压弯承载力

Key words

corrugated web/PEC column/eccentric compression test/finite element simulation/eccentric bearing capacity

引用本文复制引用

出版年

2024
建筑钢结构进展
同济大学

建筑钢结构进展

CSTPCDCSCD北大核心
影响因子:0.806
ISSN:1671-9379
段落导航相关论文