首页|利用综合管廊排风的余热供冷系统性能分析

利用综合管廊排风的余热供冷系统性能分析

扫码查看
提出一种利用综合管廊排风的余热供冷系统,对余热供冷系统的可行性、制冷性能进行分析.室外空气流经综合管廊通风区间后,排风温度有所降低.将综合管廊低温排风代替室外空气作为风冷热泵机组的冷源,可有效提高机组制冷能效,余热供冷系统可行.与传统风冷热泵相比,余热供冷系统制冷性能系数更高,波动更小.测试时间余热供冷系统最大节电率达11.9%,平均节电率约5.9%.
Performance Analysis of Waste Heat Cooling System Using Exhaust of Utility Tunnel
A waste heat cooling system using the exhaust of utility tunnel is proposed.The feasibility and refrigeration performance of the waste heat cooling system are analyzed.After the outdoor air flows through the ventilation section of the utility tunnel,the exhaust temperature is reduced.Replacing outdoor air with low-temperature exhaust from the utility tunnel as the cold source for air-cooled heat pump units can ef-fectively improve the refrigeration efficiency of the u-nits,and the waste heat cooling system is feasible.Compared with traditional air-cooled heat pumps,the waste heat cooling system has higher refrigeration per-formance coefficient and smaller fluctuations.During the testing period,the maximum power saving rate of the waste heat cooling system reaches 11.9%,and the average power saving rate is about 5.9%.

utility tunnellow-temperature ex-haustair-cooled heat pump unitrefrigeration perform-ance

邰传民、田贯三、雷文君

展开 >

山东建筑大学热能工程学院,山东济南 250101

综合管廊 低温排风 风冷热泵机组 制冷性能

山东省高等学校青创人才引育计划

鲁教[2021]51号

2024

煤气与热力
中国市政工程华北设计研究院 建设部沈阳煤气热力研究设计院 北京市煤气热力工程设计院有限公司

煤气与热力

影响因子:0.559
ISSN:1000-4416
年,卷(期):2024.44(2)
  • 15