Environmental and Economic Analysis of Central Heating Using Photovoltaic Power Generation
Combined with the engineering ex-ample,the environmental protection and economy of the electrode boiler+water heat storage central heating system using photovoltaic power generation are ana-lyzed.The energy cost per unit heating area of the e-lectrode boiler+water heat storage system is 35.3 yuan/m2,and the heating cost is high.Compared with the gas boiler room,the carbon emissions of the elec-trode boiler+water storage system during the heating period are reduced by 99.1%.The environmental ben-efit of the electrode boiler+water heat storage system is obvious,and if the carbon emission trading income is considered,the heating cost of the project will be fur-ther reduced.
photovoltaic power generatione-lectrode boilerwater heat storageenvironmental pro-tectioneconomy