武汉地埋管地源热泵系统能效测试分析
Energy Efficiency Testing and Analysis of Buried Pipe Ground-source Heat Pump System in Wuhan
胡志高 1胡平放 2王彦芳 1康杰 1朱娜 2雷飞2
作者信息
- 1. 湖北风神净化空调设备工程有限公司,湖北 武汉 430060
- 2. 华中科技大学环境科学与工程学院,湖北 武汉 430074
- 折叠
摘要
对武汉部分公共建筑地埋管地源热泵系统运行参数进行测试,对系统能效水平进行评价.将传统供能系统(常规水冷冷水机组+天然气锅炉)作为比较对象,计算地埋管地源热泵系统节能率.部分项目的热泵系统制冷、制热性能未能达标,但差距不大.热泵机组供回水温差普遍偏小.项目水泵能耗水平优于全国实测水平,但少数项目水泵能耗偏高.各项目的节能率为17.0%-50.9%,平均节能率为31.0%,节能性比较好.
Abstract
The operating parameters of the bur-ied pipe ground-source heat pump system in some pub-lic buildings in Wuhan were tested,and the energy effi-ciency level of the system was evaluated.The tradition-al energy supply system(conventional water-cooled chiller+natural gas boiler)was used as the compari-son object to calculate the energy saving rate of the buried pipe ground-source heat pump system.The re-frigeration and heating performance of some heat pump systems in certain projects did not meet the standards,but the difference was not significant.The difference in water temperature between the supply and return of heat pump units is generally small.The energy con-sumption level of water pumps in the project is higher than the national measured level,but a few projects have higher energy consumption of water pumps.The energy-saving rate of each project is 17.0%-50.9%,with an average energy-saving rate of 31.0%,indica-ting good energy-saving performance.
关键词
地埋管地源热泵/能效水平/节能率/后评估Key words
buried pipe ground-source heat pump/energy efficiency level/energy saving rate/post-evaluation引用本文复制引用
出版年
2024