首页|双蒸发温度温湿度独立控制空调系统热力学分析

双蒸发温度温湿度独立控制空调系统热力学分析

扫码查看
提出一种基于冷回收的双蒸发温度温湿度独立控制空调系统(简称THIC空调系统),建立传统空调系统、THIC空调系统热力学模型.以北京市某办公室作为应用对象,分析计算传统空调系统、THIC空调系统热力学特性.THIC空调系统中,高温制冷循环承担总冷负荷的71.4%,低温制冷循环承担总冷负荷的28.6%.与传统空调系统相比,THIC空调系统的总功耗降低8.8%,但由于回风量增加,THIC空调系统的风机功耗升高2.94%.与传统空调系统相比,THIC空调系统的制冷性能系数提高9.83%.冷回收器回收冷量为0.512 kW,冷回收器节能率为2.77%.与传统空调系统相比,THIC空调系统的㶲效率提高10.4%,总㶲损失减少105.84 W,降幅为 10.95%.
Thermodynamic Analysis of Dual Evaporation Temperature and Humidity Independent Control Air Conditioning System
An air conditioning system with inde-pendent control of dual evaporation temperature and humidity based on cold recovery(referred to as THIC air conditioning system)is proposed,and the thermo-dynamic models of traditional air conditioning system and THIC air conditioning system are established.Tak-ing an office in Beijing as the application object,the thermodynamic characteristics of traditional air condi-tioning system and THIC air conditioning system are analyzed and calculated.In the THIC air conditioning system,the high-temperature refrigeration cycle bears 71.4%of the total cooling load,and the low-tempera-ture refrigeration cycle bears 28.6%of the total cool-ing load.Compared with the traditional air conditioning system,the total power consumption of the THIC air conditioning system is reduced by 8.8%,but the fan power consumption of the THIC air conditioning system is increased by 2.94%due to the increase of return air volume.Compared with the traditional air conditioning system,the cooling performance coefficient of the THIC air conditioning system is increased by 9.83%.The cold recovery capacity of the cold recycler is 0.512 kW,and the energy savings rate of the cold recycler is 2.77%.Compared with the traditional air conditioning system,the exergy efficiency of the THIC air condition-ing system is increased by 10.4%,and the total exergy loss is reduced by 105.84 W with a decrease of 10.95%.

independent control of temperature and humiditydual evaporation temperaturecold recy-clingthermodynamic characteristics

胡文举、李赞欣

展开 >

北京建筑大学环境与能源工程学院,北京 102616

温湿度独立控制 双蒸发温度 冷回收 热力学特性

2024

煤气与热力
中国市政工程华北设计研究院 建设部沈阳煤气热力研究设计院 北京市煤气热力工程设计院有限公司

煤气与热力

影响因子:0.559
ISSN:1000-4416
年,卷(期):2024.44(4)
  • 9