摘要

对严寒地区某被动房供暖期热环境参数进行了 6个月的跟踪监测,分析了不同供暖阶段4户典型住户的室温和室内相对湿度的变化特征.结果表明:供暖期平均室温达到28.2℃,平均室内相对湿度为33.9%.如果供暖期室温能降低到20℃,则平均室内相对湿度能从33.9%升高到55.6%.适宜的温湿度不仅有利于人体舒适健康,而且适当降低室温还有利于降低建筑能耗,节能减排.

Abstract

The thermal environment parameters of a passive residential building in the severe cold re-gion were tracked and monitored for 6 months,and the variation characteristics of room temperature and rela-tive humidity of 4 typical households in different heat-ing stages were analyzed.The results show that the av-erage room temperature during the heating period rea-ches 28.2 ℃,and the average indoor relative humidity is 33.9%.If the room temperature can be reduced to 20 ℃ during the heating period,the average indoor rel-ative humidity can increase from 33.9%to 55.6%.Appropriate temperature and humidity are not only beneficial for human comfort and health,but also re-ducing room temperature appropriately can help reduce building energy consumption,and achieve energy con-servation and emission reduction.

关键词

被动房/室内热环境/室内温度/室内相对湿度/供暖期/严寒地区

Key words

passive residential building/indoor thermal environment/indoor temperature/indoor rela-tive humidity/heating period/severe cold region