Safety Distance between Gas Facilities and Centralized Charging Facilities for Electric Bicycles
Through qualitative discussion on centralized charging facilities for electric bicycles,it is recommended to manage them as electrical equipment.It is recommended to set a safety control range within a radius of 5 meters for gas risers,and not to install cen-tralized charging facilities or park electric bicycles.For horizontal main pipes,the main consideration is the vertical distance.When the height of the horizontal main pipe from the floor is less than or equal to 4.5 meters,the safety control range is within a radius of 5 meters,and centralized charging facilities should not be set up,nor should electric bicycles be parked;When the height of the horizontal main pipe from the floor is greater than 4.5 meters,the safety control range is within a radius of 3 meters,and centralized charging fa-cilities should not be set up,nor should electric bicy-cles be parked.
electric bicyclecentralized char-ging facilitygas facilitysafety distance