110 kV变压器高压套管绝缘受潮缺陷分析

Case Analysis of 110 kV Transformer Bushing Moisture Defiance

刘钊 周若琪 蒲倩 田小龙 刘小琰
农村电气化2024,Issue(3) :51-54.DOI:10.13882/j.cnki.ncdqh.2024.03.012

110 kV变压器高压套管绝缘受潮缺陷分析

Case Analysis of 110 kV Transformer Bushing Moisture Defiance

刘钊 1周若琪 1蒲倩 1田小龙 1刘小琰1
扫码查看

作者信息

  • 1. 国网河北省电力有限公司保定供电分公司,河北 保定 071000
  • 折叠

摘要

文章介绍了一起通过油中溶解气体分析发现的110 kV变压器高压套管受潮缺陷的案例.根据变压器油化试验、停电高压试验、外观及解体检查情况综合分析判断出缺陷发生的部分及原因.对由于套管顶部注油孔螺栓未安装胶垫,密封不严,导致潮气入侵导致的套管绝缘受潮缺陷,提出检修建议,为此后处理同类缺陷积累宝贵经验.

Abstract

This paper introduces a moisture defect of a 110 kV transformer Bushing found by dissolved gases analysis(DGA).Based on the comprehensive analysis of the DGA,a variety of diagnostic tests and the disintegration of the equipment,the main cause has been identified.Solutions and preventive methods have been proposed,which have a practical significance to the safe operation of the transformer.

关键词

油中溶解气体/套管/受潮/局部放电

Key words

dissolved gases analysis(DGA)/transformer bushing/moisture/partial discharge