Fault Treatment and Experimental Analysis of Relay Maloperation Caused by AC-DC Interference

扫码查看
交流串入直流系统时可能引起保护装置误动作.文章基于搭建的交流串入直流电源实验模型,对一起继电器误动作事故进行分析和处理.交流电流通过主变过载联切装置长距离控制电缆的分布电容构成回路,同时因PSL-621C线路保护出口继电器不具备抗工频电压干扰的能力,导致继电器发生误动作出口跳闸.通过方案对比,提出将主变过载联切负荷装置跳闸回路经过大功率防交流继电器启动的整改方案,并结合搭建的电源模型,验证了整改后回路的安全性.
AC-DC Interference can cause maloperation of relay protection.Based on the experimental power model of AC-DC Interference,this paper analyzes and deals with a relay maloperation accident.The results show that the dampness in switch cabinet leads to the reduction of internal insulation of handcart aviation plug,which results in mutual discharge between wires,and causing the AC-DC Interference.AC current forms a loop through the distributed capacitance of long-distance control cable of the device for transformer overload cutoff,in addition,the output relay in PSL-621C protection device does not have the ability to resist AC voltage interference,then together induce the maloperation of relay.Through scheme comparison,a rectification scheme is proposed that the trip circuit of transformer overload cutoff is started by the UEG-F,and based on proposed power model,the safety of rectified circuit is verified.