农村电气化2024,Issue(4) :49-51.DOI:10.13882/j.cnki.ncdqh.2024.04.013

一起主变压器220kV侧套管渗漏油缺陷情况分析

Analysis of a Leakage Defect in the 220 kV Side Bushing of a Main Transformer

黄晓倩
农村电气化2024,Issue(4) :49-51.DOI:10.13882/j.cnki.ncdqh.2024.04.013

一起主变压器220kV侧套管渗漏油缺陷情况分析

Analysis of a Leakage Defect in the 220 kV Side Bushing of a Main Transformer

黄晓倩1
扫码查看

作者信息

  • 1. 国网福建省电力有限公司厦门供电公司,福建 厦门 361000
  • 折叠

摘要

变压器是电力系统实现电压变换的关键设备,变压器的安全稳定运行直接影响着整个电力系统网架结构的安全.文章详细阐述了一起主变压器220 kV侧套管渗油的检查处理情况,对套管进行介损及电容量试验及解体检查分析,最终确定了套管内部密封圈密封失效的设备主因,并提出后续整改建议.

Abstract

Transformers are key equipment for achieving voltage transformation in the power system,and their safe and stable operation directly affects the safety of the entire power system grid structure.This article elaborates on the inspection and treatment of oil leakage in the 220 kV side bushing of a main transformer,conducts dielectric loss and capacitance tests on the bushing,and analyzes the disassembly inspection.Finally,the main cause of the sealing failure of the inner sealing ring of the bushing is determined,and subsequent rectification suggestions are proposed.

关键词

主变压器/套管/渗漏油/密封圈

Key words

main transformer/bushing/oil leakage/sealing ring

引用本文复制引用

出版年

2024
农村电气化
中国电机工程学会

农村电气化

ISSN:1003-0867
参考文献量9
段落导航相关论文