In response to the problems of long manual temperature measurement cycles and delayed defect detection for transmission lines,an automatic alarm device for transmission line drainage plate heating has been developed.It uses a pressure ring-type thermocouple to collect temperature data and uses a GSM module to send text messages to operation and maintenance personnel.After application testing on transmission lines,the alarm success rate is 100%,the false alarm rate is less than 5%,and the error is less than 1%,improving the reliability of power supply.
drainage plateheatingautomatic alarmpressure ring type thermocouple