农村电气化2024,Issue(10) :81-84.DOI:10.13882/j.cnki.ncdqh.2312A068

变电站交直流轮换试验不间断电源装置研究

Research on AC/DC Alternating Test Uninterrusted Power Supply Device in Substation

王辉煌 张俊康 陈祥坚 叶华 王志春
农村电气化2024,Issue(10) :81-84.DOI:10.13882/j.cnki.ncdqh.2312A068

变电站交直流轮换试验不间断电源装置研究

Research on AC/DC Alternating Test Uninterrusted Power Supply Device in Substation

王辉煌 1张俊康 1陈祥坚 1叶华 1王志春1
扫码查看

作者信息

  • 1. 国网福建省电力有限公司泉州供电公司,福建 泉州 362000
  • 折叠

摘要

变电站日常运维中,在固定的维护周期内,需要在不同电源之间切换,以确保双电源的可使用性、安全性以及完整性.虽然是双电源,但是在2种电源来回切换之间还是存在短暂的断电.文章结合现场实际进行分析,研究变电站交直流轮换试验不间断电源装置,设计供电旁路,有效避免变电站交直流系统轮换过程中出现间接性停电与设备冲击,同时设置完善电气闭锁逻辑,避免误操作导致的电源短路合环事故.

Abstract

In the daily operation and maintenance of the substation,it is necessary to switch between different power sources within a fixed maintenance cycle to ensure the usability,safety and integrity of dual power sources.Although it is a dual power supply,there is still a brief power outage when switching back and forth between the two power supplies.Therefore,strictly speaking,the reliability of dual power sources is significantly enhanced compared to single power sources,but there is still a problem of intermittent power outages.we accord the actual situation on site to study the AC/DC alternating test uninterrusted power supply device in the substation,design a power supply bypass to effectively avoid indirect power outages and equipment impacts during the rotation experiment of the AC/DC system in the substation.At the same time,a complete electrical locking logic is set up to avoid power short circuit closing accidents caused by misoperation

关键词

变电站/轮换试验/不间断电源/电气防误

Key words

substation/alternating test/uninterrusted power supply/electrical error prevention